| Counter Input |
| Channels |
2 independent 32-bit counters, counter 0&1 |
| Input Type |
Isolated or non-isolated |
| Isolated Input Level |
Logic level 0:+1V max. |
| Logic level 1: +3.5 to 30V |
| Isolation Voltage |
3750Vrms |
| Non-Isolated Input Level (Programmable) |
Logic level 0: 0 to +5V (default= 0.8V) |
| Logic level 1: 0 to +5V (default= 2.4V) |
| Maximum Count |
32bit (4,294,967,295) |
| Programmable Digital Noise Filter |
2us to 65ms |
| Alarming |
alarm on counter 0 or counter 0 & 1, programmable |
| Counter Rreset Value |
programmable |
| Built-in Virtual Battery Back Up |
for Counter Value |
| Frequency Measurement |
| Input Frequency |
1Hz to 100KHz max. |
| Gate Time |
1.0 or 0.1sec, programmable |
| Digital Output |
Channels
|
2 |
| Output Type |
Source, Open-Collector |
| Output Voltage |
30V max. |
| Output Current |
30mA max |
| Interface |
| Interface |
RS-485 |
| Format |
N, 8, 1 |
| Baud Rate |
1200 ~ 115200bps |
| LED Display |
| 1 LED |
as Power/ Communication indicator |
| 5-digit readout |
Channel 0 or Channel 1 (for M-7080BD-G) |
| Power |
| Input Voltage Range |
10~30VDC |
| Power Consumption |
2.0W (M-7080B-G) / 2.2W (M-7080BD-G) |
| Protocol |
| Support Modbus and DCON Protocol |
Yes |
| Environment |
| Operating Temperature |
-25 to 75°C |
| Storage Temperature |
-40 to 85°C |
| Humidity |
5 to 95%, non-condensing |